Electric actuation of an agent cylinder and/or selector valves is accomplished by an HF electric actuator interfaced through an Autopulse Control system. This actuator can be used in hazardous environments where the ambient temperature range is between -18 to 54 degree C.
Electric actuation of an agent cylinder and/or selector valves is accomplished by an HF electric actuator interfaced through an Autopulse Control system. This actuator can be used in hazardous environments where the ambient temperature range is between -18 to 54 degree C. The HF electric actuator meets the requirements of N.E.C Class 1, Div 1, Groups B, C, D and Class II, Div 1, Groups E, F, G. 12VDC 0.57A . The HF actuator fits on the ANSUL hi flow valve or a CV-90 valve and if manual actuation is needed use manual release lever - part number 70846. IF HF actuator is needed for a CV-98 valve then use a CV-98 booster.
The HF electric actuator meets the requirements of N.E.C. Class I, Div. 1, Groups B, C, D and Class II, Div. 1, Groups E, F, G. A maximum of two HF electric actuator scan be used on a single AUTOPULSE release circuit. When utilizing only one HF electric actuator, an in-line resistor, Part No. 73606, is required in the supervised release circuit.
Ansul HF Electric Actuator (73327) specifications:
Nominal Rated Voltage
Voltage Minimum Maximum
12 VDC @ 0.57 amps 10.4 VDC* 14.0 VDC
In auxiliary or override applications, a manual-local override valve actuator or a manual cable pull actuator can be installed on top of the HF electric actuator by removing the safety cap.
An arming tool is required to reset the actuator after operation. The actuator contains a standard 1/2 in. Threaded female straight connector for electrical conduit hookup.